xROM | NOR Flash 8MB | RAM | 64MB |
---|---|---|---|
DI/DO | Max 12DI/12DO | DI Level | Passive NPN, Public Terminal Isolated |
DO Type | MOS Tube | DO Level | Transistor Output: Low Level NPN, COM Connect To Negative |
High-speed Counting | 8 Channels, Y0-Y3 Is 100KHz, Y4-Y7 Is 10KHz. High-speed Counting + High-speed Pulse < 480KHz | High-speed Pulse | Single Phase 6 Channel 60KHz, Or 2 AB 60KHz + 1 AB 10KHz, Or 2 ABZ 60KHz + 1 AB Phase 10 KHz |
High Light | 12AI 8AO PLC Touch Panel,Passive NPN PLC Touch Panel,MOS Tube HMI PLC Panel |
HMI PLC All In One Passive NPN Input Max 12AI/8AO TYPE-C Connection
The packagewill include
* 1 set of device (grey color as default) and cables
* Software and manuals are free of charge. They are available on our website or please contact our sales team for download links.
Note:
(1) The device includes functions below
-
7 inch color touchscreen
-
RS232, RS485 port
(2) 1 set of cables is free of charge. Please order in our store for additional cables.
Parameter
Dimension | 200*146*36mm |
Cutout size | 192*138mm |
Type | 7"TFT |
Feature | 60K-color resistive touch screen, supports portrait display |
RAM | 64MB |
ROM | NOR Flash 16MB |
CPU | 32bit CPU 408MHz |
DI/DO |
Max 24DI/20DO (max 16MR) |
DI/DO level |
Input: Passive NPN, public terminal isolated Transistor output: Low level NPN, COM connect to negative |
DO type and load | MOS tube: 2A/point, 4A/4 point COM, 5A/12 point COM |
Analog I/O (optional) |
Max 12AI/8AO |
AI type (optional) |
Thermocouple E/E_/K/K_/S/S_/T/T_/J/J_ / PT100/ PT1000/ NTC10K/ NTC50K/ NTC100K/ 0~10V/ 0~5V/ 0~20mA/ 4~20mA/ -5V~5V/ -10V~10V / mixed |
AO type (optional) |
0~10V /0~5V/ 0~20mA/ 4~20mA/ mixed/ -5~5V/ -10~10V (2AO for 1 minus voltage) |
High-speed counting |
Single phase 6 channel 60KHz, or 2 AB 60KHz + 1 AB 10KHz, or 2 ABZ 60KHz + 1 AB phase 10 KHz |
High-speed pulse |
8 channels, Y0-Y3 is 100KHz, Y4-Y7 is 10KHz. High-speed counting + high-speed pulse < 480KHz |
HMI Connection | Type-C HMI download port (can download PLC program through the USB penetrating function), RS232 port |
HMI optional | 1 RS485 (changed from default RS232) |
PLC Connection | 1 TYPE-C, 1 RS232 (program port) |
PLC optional |
1 RS485 or 2 RS485 COM ports (RS485 port on HMI and RS232 on PLC will be unavailable) |
PLC optional | CAN (2.0A/B) port, Ethernet port, WIFI (will occupy default RS232 port) |
HMI Software | Coolmay mView HMI Programming Software |
PLC Software | Compatible with Mitsubishi GX Developer 8.86 and WORKS 2 |
Naming rules
1. Series QM3G: QM3G-FH series
2. HMI 43FH: 4.3inch 50FH: 5inch 70FH/70HD/70KFH: 7inch 100FH: 10inch
3. Digital input and output (DI/DO) 16: 8DI 8DO 24: 12DI 12DO 38: 20DI 18DO 44: 24DI 20 DO 60: 30DI 30DO
4. Module type M: Main module of universal controller
5. Digital output (DO) type R: relay; T: trnasistor(MOS tube); RT: both relay and transistor
6. Analog input (AD) 4 channels for 43FH/50FH,12 for 70FH/HD ,16 for 70KFH/100FH
7. Analog output (DA) 2 channels for 43FH/50FH,8 for 70FH/70HD/70KFH/100FH
8. AI type E: Thermocouple E(can be customized as type K T, S or J supports negative temperature)
PT:PT100 PT1000:PT1000 NTC thermistor 10K, 50K, 100K A0: 0-20mA A4: 4-20mA V5: 0-5V
V: 0-10V V5_:-5V~5V V_:-10~10V (only 7 and 10 inch support V5_ and V_)
9. AO type A0: 0-20mA A4: 4-20mA V5: 0-5V V: 0-10V V5_:-5V~5V
V_:-10~10V(only 7 inch and 10 inch support negative voltage covers 2 channels)
10. C1 singe phase high-speed counting,C2 AB phase counting,C3 ABZ phase counting;
Normally support 6 single phase 60KHz , or 2 AB ( Z ) 60KHz + 1 AB 10KHz
11. P0:10KHz high speed pulse;P:100KHz high speed pulse;Normally 8 channels,Y0-Y3 is 100KHz,Y4-Y7 is 10KHz;That high speed counting plus high speed pulse must be withi 480KHz
12. com port optional refers to Chart 1'basic parameter
HMI |